A- Water supply system ![]()
01- Water piping ppr, pex taken from ppr to fixtures inside conduit.
02- Chlorination for Water tanks to kill legionella.
03- Water tank storage based on occupancy type and demand per capita, minimum 24hr duration.
04- Pressure of water before meter maximum 2 bars.
05- No of meters per header in dewa meter room is 5.
06- minimum meter room size is 1.5×1.5x3m, door minimum width 0.8x2m.
07- Submeter to be provided for any use like irrigation/pool, when cooling load is 1MW or gross area of 5000m2 or more.
08- Filling point no more than 2m from ground level.
09- Condensate reuse if cooling load > 350kw.
10- Water velocity in pipe 1.5m.
B- Drainage System ![]()
01- Most common 2 pipe system used (separate soil and waste piping).
02- Vent for 1st and last manholes.
03- Manholes spacing < 20m.
04- Cleanout spacing <12m.
05- Pipe slope 110mm is 1:60 , for 160mm is 1:90, for 200mm is 1:120.
06- For building <20 floors, separate last floor.
07- For building >20 floors, separate last 2 floors.
08- Minimum soil/waste stack size for building upto 7 floors is 100mm, for buildings >7floors is 150mm.
09- Minimum vent stack size for building upto 7 floors is 75mm, for buildings >7floors is 100mm.
10- Rain water free discharge in most cases, intensity 75mm/hr.
11- Manhole/gully trap inside building to be dry type.
12- Manhole sizes :
Depth upto 1.3m ‐——- 600x600mm
Depth 1.3 to 1.7m——- 800x800mm
Depth 1.7 to 2.5m —— 1m diameter
Depth 2.5 to 4m ——— 1.5m diameter
C- Fire Fighting ![]()
01- Separate piping for sprinklers and standpipe (wet risers).
02- Breaching inlets (siamese) one for sprinklers, one for wet risers, one for tank filling.
03- Fire station to be provided every 90m vertically.
04- Interconnection between fire risers for cabinets.
05- Alarm check valve only for sprinklers.
06- Loop for high zone for high rise building, low zone provided with PRV.
07- Novec system used for most of electrical rooms, only rooms with area >10m2 need automatic system.
08- Sprinklers to be provided in public toilets, not required for other toilets except upright above ceiling in case of heater provided.
09- Sprinkler provided in elevator pit, in ceiling more than 800mm void.
10- Pump room minimum size is
50gpm pump, 3x3m
100gpm pum0, 3x4m
500gpm pump, 4x4m
1500gpm pump, 5x6m
More than 1500gpm, 6x6m